1、不能改變無功需求平衡狀態
當系統無功功率缺額時,負荷的電壓特性可以使系統在較低電壓下保持穩定運行,但如果無功功率缺額較大時,為保持電壓水平,有載調壓變壓器組件動作,電(dian)(dian)壓暫時上升,將無(wu)功功率缺(que)額全部(bu)轉嫁到主網,從而使主網電(dian)(dian)壓逐漸下降,嚴(yan)重時可能引發系統(tong)電(dian)(dian)壓崩潰。因(yin)為這(zhe)個原因(yin),世(shi)界上有幾(ji)次(ci)大(da)停電(dian)(dian)事(shi)(shi)故:例如1983年(nian)(nian)12月27日(ri)(ri)的瑞(rui)(rui)典大(da)停電(dian)(dian)事(shi)(shi)故;1987年(nian)(nian)7月23日(ri)(ri)的日(ri)(ri)本(ben)(ben)東京(jing)電(dian)(dian)力系統(tong)停電(dian)(dian)事(shi)(shi)故。這(zhe)幾(ji)次(ci)大(da)事(shi)(shi)故都造(zao)成(cheng)了很大(da)的損(sun)失。瑞(rui)(rui)典大(da)停電(dian)(dian)事(shi)(shi)故使南部(bu)系統(tong)全停電(dian)(dian),停電(dian)(dian)負荷11 400 MW,占整個系統(tong)負荷的67%,電(dian)(dian)網全部(bu)恢復(fu)時間用了7小時以上,事(shi)(shi)故損(sun)失2~3億瑞(rui)(rui)典克 郎,約3000 ~5000萬美元。日(ri)(ri)本(ben)(ben)東京(jing)大(da)停電(dian)(dian)事(shi)(shi)故停電(dian)(dian)8168MW,影(ying)響用戶280萬戶,停電(dian)(dian)時間長達3小時21分(fen)鐘,兩個500 kV變(bian)電(dian)(dian)站及一個275 kV變(bian)電(dian)(dian)站全站停電(dian)(dian),影(ying)響日(ri)(ri)本(ben)(ben)13條鐵(tie)路(lu)線停運達3小時50分(fen)鐘,東京(jing)地鐵(tie)及私營鐵(tie)路(lu)停運長達3小時,自來(lai)水中斷,銀行計算機(ji)系統(tong)中斷,造(zao)成(cheng)社會生活混亂。
2、影響變壓器運行的可靠性
變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)配置有(you)載調壓(ya)(ya)(ya)分接頭,降低了(le)變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)運(yun)行(xing)的(de)可靠性。 1982年,國際大(da)電網會議變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)委(wei)員會提出過(guo)一份(fen)報告,特別指出了(le)帶負荷調節電壓(ya)(ya)(ya)的(de)分接頭,不僅自(zi)身(shen)不可靠,同時還(huan)增加了(le)變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)整(zheng)體設計的(de)復雜性。此(ci)外,有(you)載調壓(ya)(ya)(ya)變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)由于帶負荷調整(zheng)電壓(ya)(ya)(ya),不可避免地產(chan)生電弧,其積聚(ju)游離(li)變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)油使有(you)載調壓(ya)(ya)(ya)變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)中(zhong)的(de)瓦斯冒出,有(you)時還(huan)會引(yin)起誤動作(zuo)或誤發信號。因此(ci),大(da)容量變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)配置了(le)有(you)載調壓(ya)(ya)(ya)分接頭,的(de)確給變(bian)(bian)壓(ya)(ya)(ya)器(qi)(qi)(qi)的(de)可靠運(yun)行(xing)造成了(le)一定的(de)影響。
3、加大投(tou)資(zi)及(ji)運行費用
變壓器配置了有載調壓分接頭后,體積上要比同容量的變壓器大,不僅增加了變壓器的投資,同時也增加了運行維護費用,另一方面在檢修調壓箱時,停電所需時間也較長。例如,一臺SCZ-800/10型10 kV干式有載調壓變壓器約30萬元,而一臺SC-800/10型10 kV無載調壓變壓器才約20 萬元,增加了投資約1/3。一臺110 kV,40 MVA有載調壓主變壓器約155萬元,比相同容量無載調壓變壓器的設計更為復雜,價格也相對較高。另外,頻繁動作有載分接開關及其傳動機構也增加了運行管理(li)及維護(hu)費用。
0415-6134555
0415-6256999
lnjldq@lnjldq.com
遼寧省丹東市振(zhen)安區同興工業(ye)園